Rubber Vibration Isolator Engineering Case Study II
2026-10-15
Case Detail
-
Executive Summary
Core judgment: For a 55 kW screw air compressor running at 2,950 r/min, shear-type rubber isolators with a natural frequency of about 8 Hz yield a frequency ratio r ≈ 6.2, a theoretical transmissibility of about 2.7%, and an isolation efficiency of about 97.3%. Because the compressor operates in an oil-mist environment, an oil-resistant rubber compound (NBR) is mandatory; a flexible discharge connection and rigid, separate mounting of the air receiver prevent secondary sound paths.
Conclusion: Mount the compressor skid on an inertia base with 6 isolators rated at ≥ 400 kg per point (design load ≈ 347 kg/point). The calculated performance exceeds that of the pump-unit case (r ≈ 5.4, efficiency ≈ 96.4%) because of the higher running speed, and the broadband rotor-meshing harmonics are also well attenuated.
Basis:
-
GB 50019-2015 requires the ratio of equipment running frequency to isolator natural frequency to be ≥ 2.5, and recommends rubber or other elastic-material isolators when equipment speed exceeds 1,500 r/min.
-
Disturbing frequency f = 2,950/60 ≈ 49.2 Hz; with f0 = 8 Hz, r ≈ 6.15, T = 1/(r²−1) ≈ 0.027, isolation efficiency ≈ 97.3%, force transmission reduction ≈ 31.3 dB (undamped formula).
-
The 2nd harmonic (rotor-meshing) frequency is 98.3 Hz, giving r ≈ 12.3 and T ≈ 0.7% — broadband content is isolated even more effectively.
-
A vendor compressor case reports about 90% isolation efficiency with foundation vibration below 2.5 mm/s RMS (third-party claim).
Constraints: Calculations use an undamped single-DOF model; in practice rubber damping and piping-borne secondary transmission affect results, so field re-measurement governs. Oil mist and discharge heat degrade ordinary rubber, so an oil-resistant compound and periodic aging inspection are required.
Action: Execute the workflow “measure speed → calculate frequency ratio → select model by load → install on inertia base with flexible connections → re-measure and accept”; additionally verify oil-resistance of the rubber compound and the separate rigid mounting of the air receiver.
-
Case Overview and Isolation Objectives
-
Project Background
A plant compressor room houses one 55 kW oil-injected screw air compressor on a factory skid (compressor, oil–gas separator, and control panel as one assembly), adjacent to a product inspection area and offices. Rotor-meshing excitation produces broadband vibration and noise (fundamental plus harmonics) that propagates through the floor slab and the discharge piping; field measurements showed excessive micro-vibration in the inspection area and excessive noise in the adjacent office, calling for a vibration-isolation retrofit. This document is a typical engineering case (equipment parameters are replaceable); all calculations and parameters are annotated with their source or basis.
-
Isolation Objectives and Acceptance Criteria
|
Objective
|
Indicator
|
Target/Limit
|
Basis
|
|---|---|---|---|
|
Frequency ratio
|
r = f/f0
|
≥ 2.5, preferably 4~5
|
GB 50019-2015, Cl. 12.3.4
|
|
Isolation efficiency
|
I = 1 − T
|
≥ 93% (at r ≥ 4)
|
GB 50019-2015 commentary
|
|
Vibration transmissibility
|
T
|
≤ 0.1
|
Engineering practice / vendor case figures
|
|
Noise in adjacent office
|
Daytime equivalent level
|
≤ 45 dB(A)
|
Project target (office area)
|
Sources: GB 50019-2015 “Code for Design of Heating Ventilation and Air Conditioning for Industrial Buildings”; GB 22337-2008 “Emission Standard of Environment Noise for Social Life” | Targets are common engineering values; follow project-specific requirements
-
Vibration Source Analysis and Isolation Calculation
-
Equipment Vibration Parameters and Isolation Form Selection
|
Item
|
Speed (r/min)
|
Disturbing frequency f = n/60 (Hz)
|
Recommended treatment
|
|---|---|---|---|
|
Screw air compressor (skid)
|
2 950
|
49.2
|
Shear-type rubber isolators (speed > 1,500 r/min)
|
|
Rotor-meshing 2nd harmonic
|
—
|
98.3
|
Even higher frequency ratio, well isolated
|
|
Air receiver (static)
|
0
|
—
|
Rigid mounting on floor, connected via flexible hose
|
Source: GB 50019-2015, Cl. 12.3.4; disturbing frequency computed as f = n/60
-
Frequency Ratio and Transmissibility Calculation: r ≈ 6.2, Isolation Efficiency ≈ 97%
Disturbing frequency: $$f = n/60 = 2950/60 approx 49.2 mathrm{Hz$$
Shear-type rubber isolators with an oil-resistant compound provide a natural frequency of about 8 Hz; this case assumes $$f_0 = 8 mathrm{Hz$$.
Frequency ratio: $$r = f/f_0 = 49.2/8 approx 6.1$$
Undamped transmissibility: $$T = 1/(r^{2}-1) = 1/(6.15^{2}-1) approx 0.02$$
Isolation efficiency: $$I = (1-T) times 100% approx 97.3$$; force transmission reduction: $$R = 20 lg(1/T) approx 31.3 mathrm{dB$$
2nd harmonic (rotor-meshing): $$f_2 = 2f = 98.3 mathrm{Hz$$, $$r_2 = 98.3/8 approx 12.$$, $$T_2 approx 0.7$$ — the broadband content is attenuated even more strongly.
Fig. Transmissibility and isolation efficiency vs frequency ratio (calculated curve) | Basis: undamped single-DOF model T = 1/(r²−1), sampled at r = 1.5~10; GB 50019-2015 requires r ≥ 2.5, and its commentary notes efficiency >93% at r = 4~5, with diminishing returns beyond r = 5
Conclusion: r ≈ 6.2 falls in the “efficiency >97%” region; because the frequency ratio is higher than in the pump-unit case, the screw compressor achieves better isolation with the same isolator family, and its harmonic content is isolated even more effectively.
-
Isolator Selection
-
Selection Principle for the Compressor Environment
Per the selection ranges in the “Code for Design of Noise Control in Industrial Enterprises” and the GB 50019-2015 commentary, shear-type rubber isolators (natural frequency 5~12 Hz) suit medium/high-speed equipment; metal springs (2~5 Hz) are intended for equipment at or below 1,500 r/min, and air springs (1~8 Hz) for precision low-frequency isolation. For this compressor, rubber is the economical choice and its internal damping additionally controls the startup passage through resonance.
|
Isolation form
|
Natural-frequency range
|
Suitability here
|
|---|---|---|
|
Shear-type rubber isolator
|
5~12 Hz
|
Chosen: f0 ≈ 8 Hz, high damping, economical
|
|
Metal spring isolator
|
2~5 Hz
|
Not required: speed > 1,500 r/min; low damping
|
|
Rubber isolation pad
|
10~20 Hz
|
Only as auxiliary layer, not primary isolation
|
|
Air spring isolator
|
1~8 Hz
|
Over-specified and costly for this application
|
Source: isolation ranges from the “Code for Design of Noise Control in Industrial Enterprises” and GB 50019-2015 commentary
-
Load Calculation and Model Selection
The compressor skid (compressor + separator + control panel + steel base) weighs about 1,600 kg; with 6 mounting points, the static load is about 267 kg per point. Applying a dynamic factor of 1.3 for startup torque and load redistribution gives a design load of about 347 kg per point.
Selection follows “rated load ≥ design load, and deflection not exceeding 1/3–1/2 of the ultimate deflection”. Selection result:
|
Item
|
Value
|
Note
|
|---|---|---|
|
Mounting points
|
6 (symmetrical)
|
Skid corners plus mid-span points
|
|
Static load per point
|
≈ 267 kg
|
1,600 kg / 6
|
|
Design load per point
|
≈ 347 kg
|
Dynamic factor 1.3
|
|
Selected rated load
|
≥ 400 kg
|
Shear-type, NBR compound
|
|
Target natural frequency
|
≈ 8 Hz
|
gives r ≈ 6.2
|
Basis: rated-load matching with manufacturer parameter tables (e.g., E-type series); oil-resistant NBR compound required by the oil-mist environment | Values are case assumptions and calculations, not measured data
-
Why Rubber Rather Than Springs for This Compressor
|
Dimension
|
Rubber isolator (chosen)
|
Metal spring isolator
|
|---|---|---|
|
Natural frequency
|
≈ 8 Hz (shear type)
|
2~5 Hz
|
|
Damping
|
High internal damping (ζ ≈ 0.05~0.15), controls startup resonance
|
Low damping; large resonance amplitude at startup
|
|
Cost and simplicity
|
Low, direct mounting
|
Higher, often needs added dampers
|
|
Oil/heat resistance
|
NBR compound; needs protection and inspection
|
Durable; corrosion protection needed
|
Source: combined from code selection ranges and engineering experience
-
Installation Implementation
-
Base and Foundation
-
Weld a steel inertia base beneath the skid to stiffen it and distribute load; level the base so that the center of gravity is as close as possible to the geometric center of the 6-point isolator array and the overall CG is low (GB 50019-2015, Cl. 12.3.5).
-
Where the inspection area is extremely sensitive, add a “floating double-isolation base”: a precast concrete slab between the equipment base and the floor, with rubber isolation pads beneath the slab (Cl. 12.3.8).
-
Mount the air receiver rigidly on the floor as a separate item — do not place it on the isolators, so it does not rock and re-radiate vibration.
-
Isolator Installation Requirements
-
Design compression deflection should be taken as 1/3–1/2 of the manufacturer's ultimate deflection; no isolator may exceed its allowable working load (Cl. 12.3.4).
-
Check that deflection is equal across all 6 points after installation; a flexible skid redistributes load if leveling is poor, causing uneven deflection and rocking modes.
-
Use an oil-resistant (NBR) compound; shield isolators from oil mist, discharge heat, and direct sunlight, and include deflection/aging checks in the annual maintenance plan.
-
Piping, Discharge Connection, and Structure-Borne Sound Control
-
Connect the compressor discharge to the piping via a rubber flexible connector; install elastic pads between pipe supports/hangers and the piping; seal gaps where pipes pass through the compressor-room enclosure with sound-insulating elastic material (Cl. 12.3.6, Cl. 12.3.7).
-
Connect the air receiver to the discharge piping through a flexible hose so that receiver pulsations are not transmitted back to the isolated skid or to the building.
-
Performance Verification and Case Data
-
Before/After Comparison
|
Indicator
|
Before retrofit
|
After retrofit
|
Data nature & source
|
|---|---|---|---|
|
Vibration transmissibility
|
Rigid mounting, near 1
|
< 5% (calculated T ≈ 2.7%)
|
Undamped formula, this case
|
|
Isolation efficiency
|
—
|
≈ 97.3% (calculated)
|
Undamped formula, this case
|
|
Foundation vibration
|
Excessive
|
< 2.5 mm/s RMS
|
Vendor compressor case (third-party claim)
|
|
Noise in adjacent office
|
Exceeded 45 dB(A)
|
Reduced; meets project target
|
Project measurement (planned)
|
Sources: see references at the end of this document | Calculated values are undamped-model results; vendor figure is a third-party claim for reference only; acceptance is based on field measurement
Conclusion: at r ≈ 6.2 the screw compressor case reaches a higher isolation efficiency (≈97.3%) than the pump case (≈96.4%) thanks to the higher running speed, and the 2nd-harmonic content is attenuated to below 1% transmissibility.
-
Acceptance Conclusion
Recheck the calculation against GB 50019-2015 (frequency ratio ≥ 2.5), then re-measure vibration velocity, transmissibility, and adjacent-office noise after the retrofit: acceptance is granted when the targets are met. Record isolator deflection, base levelness, the condition of flexible connections, and the oil-resistance/aging status of the rubber.
-
Lessons Learned and Notes
-
Higher running speed makes isolation easier: r ≈ 6.2 here versus r ≈ 5.4 for the pump, with efficiency rising from about 96% to about 97%.
-
Screw compressors emit broadband rotor-meshing vibration; rubber damping not only isolates but also controls the startup passage through resonance, which low-damping springs would amplify.
-
Oil mist and discharge heat are the main rubber killers: use an NBR compound, shield the isolators, and inspect for aging and deflection annually.
-
On a flexible skid with 6 mounting points, leveling and equal deflection are critical; otherwise load redistribution creates rocking modes and uneven compression.
-
Isolation addresses only the “equipment–foundation” path: the discharge pipe, supports, wall penetrations, and a rigidly mounted receiver must be treated, or secondary sound paths undermine the retrofit.
-
Calculations use an undamped model; actual rubber damping ratios of about 0.05–0.15 suppress resonance amplitude, and the above formulas are adequate for engineering judgment.
-
References